16 OPERATIONS TO BE CARRIED OUT IN CASE OF ALARM
1. Press ACK.
2. Read the point in alarm on the display.
3. Go and check the possible alarm on the field. If no problems are detected or no real danger exists press
RESET.
Should the alarm persist it is possible to exclude the point as follows:
1. Press ACK.
2. Read the point in alarm on the display.
3. Press INCLUDE/EXCLUDE.
4. Select the option INCLUDE/EXCLUDE POINTS/ZONES
5. Select the option INCLUDE/EXCLUDE POINTS
6. Select the circuit where the point to be excluded is located by operating ∧ and ∨
7. Press OK
8. Select the point to be excluded by entering the address or using keys ∧ and ∨ or typing in the address on the
numerical keypad
9. Press OK
10. Select EXCLUDED through ∧ and ∨
11. Press OK
12. Press ESC until a message indicating the excluded point is displayed
13. Press RESET.
To include a previously excluded point proceed as follows:
1. Press INCLUDE/EXCLUDE.
2. Select the option INCLUDE/EXCLUDE POINTS/ZONES
3. Select the option INCLUDE/EXCLUDE POINTS
4. Select the circuit where the point to be included is located by operating ∧ and ∨
5. Press OK
6. Select the point to be included by entering the address or using keys ∧ and ∨ or typing in the address on the
numerical keypad
7. Press OK
8. Select INCLUDED through ∧ and ∨
9. Press OK
10. Press ESC
until the control panel goes back to the messages shown during the scanning phase and the
message related to the excluded point is not shown anymore
11. Press RESET.
17 OPERATIONS TO BE CARRIED OUT IN CASE OF FAULT
1. Press ACK.
2. Read the cause of fault on the display.
3. Go and check the possible fault on the spot. If no problems are detected or no real danger exists press
RESET.
4. Should the fault persist press ACK and contact service.