18.7 APPENDIX 7 – FAULT CODES FOR SLAVE CONTROL PANELS
If a slave control panel undergoes a fault during the scanning phase, the user is notified with the following message:
FAULT SLAVE PANEL XXX (YY)
NAME OF THE SLAVE CONTROL PANEL
XXX = address of the slave control panel affected by the fault
YY = fault code
The table below reports the fault codes along with the relevant explanation:
Code Fault
1 Missing communication (the slave control panel does not answer)
2 Slave control panel continuously busy in not interruptible operations
3
Slave control panel busy in processing commands received by other sources
(USB/Ethernet/Modem)
4 Slave control panel not recognizing the command
5 The slave control panel deems an actually correct command with parameter errors
18.8 APPENDIX 8 – LIST OF PC SUBCOMMANDS (CMD “EXECUTE ACTION”)
When the control panel in scanning phase is connected to a PC, it can receive the command “execute action”.
By means of this command, the PC can ask the control panel to execute specific actions.
Every time this command is received, an event is stored into the event log and will be shown to the user with a
message like this;
COMMAND EXECUTION XXX
Where:
XXX = identifier of the subcommand
The following table reports the subcommand identifiers.
Code Action
0 Global Reset
1 Acknowledge
2 Silence Siren
3 Restore Siren
4 General Alarm
5 Testlamp
6 Cancel delay
7 Increase delay
8 Maintenance

Other manuals for Elkron FAP54