FAP User 19
The following table contains the point error codes and the relevant explanation.
Code Fault
1 Smoke/heat detector: internal fault of the optical section
2 Smoke/heat detector: internal fault of the optical section (signal less than the fault threshold)
3 Internal fault of the temperature detection section
4 Smoke detector: error at the end of the optical calibration procedure
5 Smoke detector: optical calibration is missing because of out of range temperature
6 Internal fault: non volatile memory access error
7 Internal fault: testing not executed
8 Internal fault: optical calibration not executed
9 Internal fault: calibration failed
10 Heat detector or smoke/heat detector: internal fault of the temperature detection section.
11 Manual push button: internal fault of the alarm switch
12 External fault: analog input 1 is short circuited
13 External fault: analog input 1 is open (end of line resistor is missing)
14 External fault; analog input 2 is short circuited
15 External fault: analog input 2 is open (end of line resistor is missing)
16
External fault: missing short circuit of input 1 of a mode 2 actuator within the expected time
(feedback time)
17 External fault: alarm repetition output is short circuited
18
The point has notified an external fault, but it is not possible to read the cause because of a
communication problem
19 Type programming error
20 The point does not answer to the cyclic polling during the monitoring phase
21 The point does not answer to a command
22 The point does not answer to the initial polling at the beginning of the monitoring phase
23
The point answers wrongly with a too high current to the polling during the monitoring phase
(possible answer coming simultaneously from more than one point)
24 The point type is different than the programmed one
25 Point not accepted because of wrong manufacturer code
26 The point does not answer to the adaptation command
27 The point does not answer to the status request command for inclusion verification
28 The point does not answer to the command of inclusion
30 External fault: alarm repetition/siren output is open (end of line resistor is missing)
31 External fault: alarm repetition/siren output is short circuited
32 External fault: electrical overloaded on the gemma output
33 External fault: external power supply applied to a point programmed to work without it
34 External fault: external power supply missing on a point programmed to work with it
35
External fault: the value read is lower than the threshold of fault of the analog section (possible
break of the electric connection with the measurement equipment)
36 External fault: conventional detection circuit is short circuited
37 External fault: conventional detection circuit is open (end of line resistor is missing)
38 Dip-switch configuration on the device is different than the one programmed in the control panel
40 -43
Failure of the attempt to recovery communication with the point after a missing answer to the
cyclic polling during the monitoring phase