EasyManua.ls Logo

ELSA 3L-SP - 2.2 ENVIRONMENTAL RATINGS; 2.3 POWER REQUIREMENTS; 2.4 POWER RELAYS SWITCHING CHARACTERISTICS; 2.5 SUPERVISING CHANNEL

ELSA 3L-SP
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
2.2 ENVIRONMENTAL RATINGS
Operating temperature : 0⁰C to 40⁰C (indoor installation only)
Storage temperature : -20⁰C to 70⁰C
Humidity : 5% to 95% non-condensing
2.3 POWER REQUIREMENTS
Power supply : 100-240 VAC, 50/60 Hz
Optional input : 12 to 30 VAC/DC power input
Power consumption : 8VA/3 W maximum
2.4 POWER RELAYS SWITCHING CHARACTERISTICS
Cable break/power failure by contact (1 relay) : Operation SPDT
Switching current -0.5 A at 250 VAC, 1A at 30 VDC
Liquid leakage dry contact : Operation SPDT
Switching current -0.5 A at 250 VAC, 1A at 30 VDC
2.5 SUPERVISING CHANNEL
Physical support : RS485-two-wire, ESD and surge protected as per IEC 61000-4-2
Protocol : Modbus
2.6 SERIAL COMMUNICATION INTERFACE
Physical support : RS485-two-wire, ESD and surge protected as per IEC 61000-4-2
Protocol : Modbus
Operational GSM/GPRS transmitter interfacing
Optional Modbus over TCP/IP (allow world-wide remote supervision through Internet connection)
Optional BACnet/IP interface
Optional Profibus interface
Optional LONworks interface
2.7 COMPLIANCE TO INTERNATIONAL STANDARDS
EMC emission : IEC61000-6-3(2001) Electromagnetic compatibility Generic emission
standard for residential, commercial and light industrial environment
EMC immunity : IEC61000-6-1(2001) Electromagnetic compatibility Generic immunity
standard for residential, commercial and light industrial environment