06/2022
| 52 |
924EHUCE4.00 - Mistral Humidier
The Mistral humidifier features:
• Automatic draining for inactivity;
• Periodic automatic cleaning;
• Plastic material on whose surface bacterial colonies do not proliferate.
Inadequate use and/or poor maintenance of the humidifier can damage your health.
WARNING
BIOLOGICAL RISK
• In the event of inadequate use and/or poor maintenance it is possible that microorganisms (including the bacterium that
causes Legionellosis) may proliferate and be transferred into the air treatment system.
• Thehumidifiermustbeusedproperlyandbemaintainedandcleanedproperlyatprescribedintervals,asdescribedin
chapter "10. MAINTENANCE" ON PAGE 51.
10.3 CLEANING THE RESERVOIR
Cleaningandmaintenanceofthereservoirmustbedoneevery60dayswhenusingnon-demineralizeddrinkingwaterto
ensure optimal operation of the humidifier. With demineralized water the cleaning frequency is seasonal.
This procedure is useful to prevent the water drain from clogging.
Below are the cleaning instructions:
• Drainthehumidier(see"9.1 DRAINING WATER / WASHING RESERVOIR" ON PAGE 41);
• Disconnect the machine power supply using the external isolator;
• Unscrewthescrewsatthetopofthehumidier;
• Clean the reservoir;
• Checkthecoversealisintact;
• Install the cover by screwing the screws into the upper face.
Fig. 45. Opening the Mistral cover to clean the reservoir