Quick Start Guide Minipack PS System
356808.103, v1-2006-12
14
Mains Feeds versus Rectifier ID
Mains Monitoring
The Minipack system is fed with 3 One-phase 230VAC Mains input circuits.
Each input circuit is internally connected to feed 2 rectifiers, in such a
pattern that loads the 3 circuits evenly.
Plug-and-Play Rectifiers versus Mains Monitoring
When a rectifier is hot plugged in a power shelf for the first time, the Smartpack controller
assigns the next available ID number to the rectifier, starting with “01”.
When a previously installed (hot plugged) Minipack rectifier is inserted in a power shelf, the
Smartpack controller “recognizes” the module, and assigns the same ID to the rectifier. In other
words, the controller and the rectifier “remember” the assigned ID number, even after removing
and reinserting the rectifier in the shelf.
To achieve a more controlled ID assignment, you should always insert & hot-plug new Minipack
rectifiers in the power shelf, one module at a time, in following shelf position order: 1, 3, 5 and
2, 4, 6.
This position-versus-ID number relationship is very important for the correct monitoring of the
mains circuit, as the Smartpack controller always uses rectifier ID01, 02 and 03 to monitor the
Mains Feed 1, 2 and 3 respectively. If these rectifiers malfunction, rectifier ID 04, 05 and 06 will
automatically take over.
For example: accidentally inserting a rectifier with ID02 in a power shelf position internally
connected to mains feed 1, will cause the controller to monitor mains feed 1 “thinking“ it monitors
mains feed 2.
Miscellaneous
AC Mains
Position #
1
2 3 4 5 6
ID #
01
04
02
05
03
06
Mains Feed 1
One-
p
hase, 230VAC
N
(L2)
230VAC
AC
Mains
L
(L1)
01 02
Mains Feed 2
One-
p
hase, 230VAC
N
(L2)
230VAC
AC
Mains
L
(L1)
03 04
Mains Feed 3
One-
p
hase, 230VAC
N
(L2)
230VAC
AC
Mains
L
(L1)
05 06
Distribution of Minipack rectifiers (ID #)
on the 3 AC Mains Input Circuits
01
Mains Feed
2
Mains Feed 1
Mains Feed
3
02 03
Minipack
System
Position 6
ID number
(Assigned CAN
bus address)
04 05 06