3.8 Analog interface
The analog interface allows the generator to be integrated into an SPC or
into another environment using 0…10 V or 0…20 mA interfaces.
Caution!
• To avoid damaging the generator, make sure that the signals are con-
nected correctly.
• Fusing protection for the fault alarm contact must be provided by the
customer.
• Shielded cables must be used to wire the analog interface; the shield
must make contact on both sides.
3.8.1 Variant with connecting terminals
Pin assignment ST15
7/8/9Floating contact (fault alarm contact):
Output depending on parameter <Limit Signal>:
1. case: <Limit Signal = NO>: contact opens in the event of
malfunction (chap. 7).
2. case: <Limit Signal = YES>: contact opens in the event of
malfunction and when reaching the current or voltage limit.
max. 24 V / 0.5 A DC / AC
mains off: Relay indicating fault
Fig. 8:
Pin assignment,
connecting
terminals
Z01110y
Fig. 9:
Representation of
no-fault status
(switched on)
Z01108y