EasyManua.ls Logo

Emerson 2404 - Frequency Reference Selected; Pre-Skip Filter Reference; Reference Offset; Maximum Set Speed

Emerson 2404
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Menu 1 Introduction
Parameter
x.00
Parameter
description format
Keypad and
display
Serial
communications
CT Modbus
RTU
PLC Ladder
programming
CTSoft Menu 0
Advanced parameter
descriptions
38 Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Indication of the reference being used by the drive for system setup and fault finding.
Indication of the reference being used by the drive for system setup and fault finding.
See Pr 1.09 on page 39.
Reference used for jogging. See section 10.7 Menu 6: Drive sequencer and clock for details on when the jog mode can be activated.
This parameter is a symmetrical limit on both directions of rotation.
Defines drive absolute maximum frequency reference. Slip compensation and current limit can increase the motor frequency further.
1.01 Frequency reference selected {81}
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111 1 1
Range ±550 Hz
Update rate 5ms
1.02 Pre-skip filter reference {82}
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111 1 1
Range ±550 Hz
Update rate 5ms
1.03 Pre-ramp reference {83}
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111 1 1
Range ±550 Hz
Update rate 5ms
1.04 Reference offset
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
11 11
Range ±550 Hz
Default 0.0
Update rate 5ms
1.05 Jog reference {15}
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 111
Range 0.0 to 400.0 Hz
Default 1.5
Update rate 5ms
1.06 Maximum set speed {02}
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 111
Range 0.0 to 550 Hz
Default
Eur: 50.0
USA: 60.0
Second motor
parameter
Pr 21.01
Update rate Background

Table of Contents

Related product manuals