Menu 5 Introduction
Parameter
x.00
Parameter
description format
Keypad and
display
Serial
communications
CT Modbus
RTU
PLC Ladder
programming
CTSoft Menu 0
Advanced parameter
descriptions
72 Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
10.6 Menu 5: Motor control
Table 10-7 Menu 5 parameters: single line descriptions
*18kHz is only available on Commander SK size A to C, 200V units.
Parameter Range
Default
Setting Update Rate
Eur USA
5.01 Motor frequency {85} ± 550 Hz
21 ms
5.02 Motor voltage {86}
0 to AC_VOLTAGE_MAX V
B
5.03 Output power ±POWER_MAX kW
B
5.04 Motor speed {87} ± 9999 rpm
B
5.05 DC bus voltage {84}
0 to +DC_
VOLTAGE_MAX V
B
5.06 Motor rated frequency {39} 0.0 to 550.0 Hz 50.0(Eur), 60.0(USA) B
5.07 Motor rated current {06}
0 to RATED_
CURRENT_MAX A
Drive rated current
{Pr 11.32}
B
5.08 Motor rated full load rpm {07} 0 to 9999 rpm
1500(Eur), 1800(USA)
B
5.09 Motor rated voltage {08}
0 to AC_
VOLTAGE_SET_
MAX V
110V drive: 230
200V drive: 230
400V drive: 400(Eur)
460(USA)
575V drive: 575
690V drive: 690
128 ms
5.10 Motor rated power factor {09} 0.00 to 1.00 0.85 B
5.11 Number of motor poles {40}
Auto(0), 2P(1), 4P(2),
6P(3), 8P(4)
Auto(0) B
5.12 Auto-tune {38} 0 to 2 0 B
5.13 Dynamic V to F select {32} OFF(0) or On(1) OFF(0) B
5.14 Voltage mode select {41}
Ur S(0), Ur(1), Fd(2), Ur
A(3), Ur I(4), SrE(5)
Ur I(4) Fd (2) B
5.15 Low frequency voltage boost {42}
0.0 to 50.0% of motor
rated voltage
3.0 1.0 B
5.16 Not used
5.17 Stator resistance 0.000 to 65.000 Ω 0.000 B
5.18 Maximum switching frequency {37} 3(0) to 18kHz(3)* 3(0) B
5.19 High stability space vector modulation OFF(0) or On(1) OFF(0) B
5.20 Over modulation enable OFF(0) or On(1) OFF(0) B
5.21 Not used
5.22 Not used
5.23 Voltage offset 0.0 to 25.0 V 0.0 B
5.24
Transient inductance (σL
s
)
0.00 to 320.00 mH 0.00 B
5.25 Not used
5.26 Not used
5.27 Enable slip compensation OFF(0) or On(1) On(1) B
5.28 Not used
5.29 Not used
5.30 Not used
5.31 Not used
5.32 Not used
5.33 Not used
5.34 Speed display units {23} Fr(0), SP(1), Cd(2) Fr(0) B
5.35 Disable auto-switching frequency change OFF(0) or On(1) OFF(0) B
5.36 Not used
5.37 Actual switching frequency 3 to 18kHz BW
5.38 Not used
5.39 Not used
5.40 Not used
5.41 Not used
5.42 Not used
5.43 Not used
5.44 Not used
5.45 Not used
5.46 Not used
5.47 Not used
5.48 Not used
5.49 Not used
5.50 Security unlock 0 to 999 BR