80 Series Thermostats
37
Heat Pump Staging Applications
• 1F83C-11 Apply to Single Stage Compressor Heat Pumps with No
Auxiliary or Emergency Heat
.
– Install a jumper between Y and W and select the proper reversing valve
changeover position O or B
• 1F83H-21 or 1F85U-22 Apply to Single Stage Compressor Heat
Pumps with one stage of Auxiliary or Emergency Heat.
• 1F85U-42 Apply to Single or Two Stage Compressor Heat Pumps with
up to two stages of Auxiliary or Emergency Heat.
– The -42 allows up to two Heat Pump and two Auxiliary / Emergency stages
(four stages heat maximum). As received, -42 Universals sequence (stage)
the back-up heating terminals W/E and W2.
– There is also a menu option to use W2 as a single stage of Auxiliary Heat and
use W/E as a separate Auxiliary Heat Only (Emergency) stage. This would
result in a 3 Heat/ 2 Cool thermostat.
Model Number
(NP or PR)
HP Stages
Configure For Separate
Aux-Emergency
HP Stages With Separate
Aux/Emergency
Heat Aux Cool Heat Aux Cool
1F83C-11 1 0 1 None 1 0 1
1F83H-21 1 1 1 Clip W2/E Jumper 1 1 1
1F85U-22 1 1 1 Use Configuration Menu Item #15 1 1 1
1F85U-42 2 2 2 Use Configuration Menu Item #15 2 1 2