Installation and commissioning
[17]
Figure 5-2: DIN rail mounting
A.
EZ 1000
B.
DIN rail type NS 35/7.5
C.
Minimum required space on DIN rail: 26 mm
5.3 Hints for installation and connection
To ensure the electromagnetic compatibility of the eddy current measuring chain,
WayCon recommends using a double shielded twisted pair cable for connecting the
EZ 1000 converter to the measuring amplifier, for example to an A6500-UM Universal
Measurement Card of the AMS 6500 ATG system. For direct connections to the converter,
LiYCY-CY 2x2x0.25 mm² or equivalent cables are preferred. Master connection cable may
be any multicore cable with a corresponding cable structure. WayCon recommends
connecting the outer cable shield to protective earth/measuring ground close to the