Malfunction Possible cause Remedy
Output pressure
too low
Supply pressure too low Increase the supply pressure
Insufficient power supply for the
device
Check LEDs UA and UL on the bus
coupler and the electrical supply
plate and supply the devices with
the correct (adequate) voltage.
Air is audibly escap-
ing
Leaks between the valve system
and connected pressure line
Check the pressure line connec-
tions and tighten, if necessary.
Pneumatic connections confused Properly connect the pneumatics
for the pressure lines
Addressing via
DHCP server not
possible
A save process was triggered on
the bus coupler before the address
0x00 was set.
Perform the following four steps:
1. Disconnect the bus coupler
from the voltage and set an ad-
dress between 1 and 254 (0x01
and 0xFE).
2. Connect the bus coupler to the
voltage and wait 5 seconds, then
disconnect the voltage again.
3. Set the address switch to 0x00.
4. Re-connect the bus coupler to
the voltage.
Addressing via the DHCP server
should now work.
Wrong address set Disconnect the bus coupler from
the voltageUL and then set the
correct address g9.2.Changing
the Address
UL LED flashes red The electronics supply voltage is
less than the lower tolerance limit
(18VDC) and greater than
10VDC.
Check the power supply at plug
X1S.
UL LED illuminated
red
The electronics supply voltage is
less than 10VDC.
UL LED is off The electronics supply voltage is
significantly less than 10VDC.
UA LED flashes red The actuator voltage is less than
the lower tolerance limit
(21.6VDC) and greater than UA-
OFF.
UA LED illuminated
red
The actuator voltage is less than
UA-OFF.
MOD LED flashes
green
No connection has been estab-
lished with a master.
Configure the master so that it es-
tablishes a connection.
MOD LED flashes
red
Diagnostic message from module
present
Check modules.
MOD LED illumi-
nated red
There is no module connected to
the bus coupler.
Connect a module.
There is no end plate present. Connect an end plate.
More than 32 electrical compo-
nents are connected on the valve
side.
g12.5.3.Impermissible configu-
rations
Reduce the number of electrical
components on the valve side to
32.
Over ten modules are connected
in the I/O zone.
Reduce the number of modules in
the I/O zone to ten.
The module circuit boards are not
plugged together correctly.
Check the plug contacts of all
modules
(I/O modules, bus coupler, valve
drivers, and end plates)
A module circuit board is defec-
tive.
Exchange the defective module.
The bus coupler is defective. Exchange the bus coupler
The new module is not recog-
nized.
Contact AVENTICS GmbH (see
back cover for address)
NET LED illuminated
red
Severe network error present Check network.
IP address assigned twice Change the IP address.
NET LED flashes red Connection to master has been
disrupted. EtherNet/IP communi-
cation can no longer take place.
Check the connection to the mas-
ter.
An error was discovered in the PLC
configuration.
Check the PLC configuration.
NET LED is off A physical connection to the net-
work has not yet been established.
Establish physical connection to
the network (connect and/or
check EtherNet cable).
Neither a static nor a dynamic IP
address has been assigned.
Assign IP address.
Malfunction Possible cause Remedy
No DHCP service has been acti-
vated.
Re-activate DHCP service.
NET LED flashes
green
The network connection is in
place, but an EtherNet/IP connec-
tion has not been established.
Connect the module to an Ether-
Net/IP system.
Switch on the EtherNet/IP con-
troller.
L/A1 or L/A2 LED il-
luminated in green
(only flashes in yel-
low seldom)
No data exchange with the bus
coupler,
e.g. because the network section
is not connected to a controller
Connect the network section with
a controller.
Bus coupler was not configured in
the controller.
Configure bus coupler in the con-
troller.
L/A 1 or L/A 2 LED is
off
There is no connection to a net-
work participant.
Connect fieldbus connection X7E1
or X7E2 with a network participant
(e.g. a switch).
The bus cable is defective and no
connection can be made with the
next network participant.
Exchange the bus cable.
Another network participant is de-
fective.
Exchange network participant.
Bus coupler is defective. Exchange the bus coupler
14 Technical Data
Table29: Technical data
General data
Dimensions 37.5mm x 52mm x 102mm
Weight 0.17 kg
Operating temperature range -10°C to 60°C
Storage temperature range -25°C to 80°C
Ambient operating conditions Max. height above sea level: 2000m
Vibration resistance Wall mounting EN60068-2-6:
±0.35mm displacement at 10Hz to 60
Hz,
5g acceleration at 60Hz to 150Hz
Shock resistance Wall mounting EN60068-2-27:
30g with 18ms duration,
3 shocks each direction
Protection class according to EN60529/
IEC60529
IP65 with assembled connections
Relative humidity 95%, non condensing
Degree of contamination 2
Use Only in closed rooms
Electronics
Electronics power supply 24VDC ±25%
Actuator voltage 24VDC ±10%
Valve inrush current 50mA
Rated current for both 24V power supplies 4A
Connections Power supply for bus coupler X1S:
Plug, male, M12, 4-pin, A-coded
Ground
(FE, functional earth)
Connection according to
DINEN60204-1/IEC60204-1
BUS
Bus protocol EtherNet/IP
Connections Fieldbus connections X7E1 and X7E2:
Socket, female, M12, 4-pin, D-coded
Output data quantity Max. 512 bits
Input data quantity Max. 512 bits
Standards and directives
DINEN61000-6-2 “Electromagnetic compatibility” (Immunity for industrial environments)
DINEN61000-6-4 “Electromagnetic compatibility” (Emission standard forindustrialenvi-
ronments)