EasyManuals Logo

Emerson AVENTICS System Description

Emerson AVENTICS
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Operation without EDS file
You can also operate the system without an EDS file.
1. For this, calculate the incoming and outgoing data lengths as described in Ta-
ble 9.
2. Enter the following values in the PLC configuration program for a class1 con-
nection:
Connection:
Master slave: point-to-point
Slave master: multicast
Connection points:
Master slave: “101” and as data length “output data length”
Slave master: “102” and as data length “input data length”
Configuration: “1” and as data length “0”
5.3 Configuring the Bus Coupler in the Fieldbus System
Before you can configure the individual components of the valve system, you
need to assign an IPaddress to the bus coupler using your PLC configuration soft-
ware. In most cases, a DHCPserver assigns the address during commissioning
and subsequently permanently assigns it to the device.
1. Assign a unique IP address to the bus coupler using the planning tool
g9.3.Assigning IP Address and Subnet Mask.
2. Configure the bus coupler as a slave module.
5.4 Configuring the Valve System
5.4.1 Module sequence
The input and output data used by the modules to communicate with the con-
troller consist of a byte string. The lengths of the valve system input and output
data are calculated from the number of modules and the data width of the indi-
vidual module. The data is only counted in bytes. If a module has less than 1 byte
of input or output data, the left-over bits are “stuffed” to the byte boundary us-
ing non-information bits.
Example: A valve driver board, 2x, with 4 bits of user data occupies 1byte in the
byte string, since the remaining 4 bits are stuffed with non-information bits. The
data of the next module therefore starts after a byte boundary.
In the example (see Fig.3), the modules are numbered to the right of the bus
coupler (AES-D-BC-EIP) in the valve zone, starting with the first valve driver board
(module1) and continuing to the last valve driver board on the right end of the
valve unit (module9).
Bridge cards are not taken into account. Supply boards and UA-OFF monitoring
boards occupy one module (see module7 in Fig.3). The supply boards and UA-
OFF monitoring boards do not add any bytes to the input and output data. How-
ever, they are also counted, since they have diagnostic data, which is transferred
at the corresponding module position. The data length for pressure regulators
can be found in the operating instructions for AV-EP pressure regulators
(R414007537).
The numbering is continued in the I/O zone (module10 to module12 in Fig.3).
There, numbering is continued starting from the bus coupler to the left end.
The bus coupler’s parameter data is annexed to the output data in the byte chain.
The bit assignments of the bus coupler are described in section g5.5.Setting the
Bus Coupler Parameters.
The diagnostic data of the valve system is 8 bytes in length and is appended to
the input data. The structure of this diagnostic data is described in Table14.
Fig.3: Numbering of modules in a valve system with I/O modules
S1 Section 1 S2 Section 2
S3 Section 3 P Pressure supply
UA Power supply M Module
A Single pressure control working con-
nection
AV-
EP
Pressure regulator with 16 bits of in-
put and output data
IB Input byte OB Output byte
- Neither input nor output byte
The symbols for the valve zone components are explained in sec-
tiong12.2.Valve Zone.
Example
Fig.3 shows a valve system with the following characteristics:
Bus coupler
Section1 (S1) with 9valves
Valve driver board, 4x
Valve driver board, 2x
Valve driver board, 3x
Section2 (S2) with 8valves
Valve driver board, 4x
Pressure regulator with 16 bits of input and output data
Valve driver board, 4x
Section3 (S3) with 7valves
Supply board
Valve driver board, 4x
Valve driver board, 3x
Input module
Input module
Output module
The PLC configuration key for the entire unit is thus:
423–4M4U43
8DI8M8
8DI8M8
8DO8M8
The data lengths of the bus coupler and the modules are shown in Table9.
Table7: Calculation of the valve system data lengths
Module
number
Module Output data Input data
1 Valve driver board, 4x 1 byte of user data
2 Valve driver board, 2x 1 byte
(4bits of user data plus
4filler bits)
3 Valve driver board, 3x 1 byte
(6bits of user data plus
2filler bits)
4 Valve driver board, 4x 1 byte of user data
5 Pressure regulator 2 bytes of user data 2 bytes of user data
6 Valve driver board, 4x 1 byte of user data
7 Electrical supply
8 Valve driver board, 4x 1 byte of user data
9 Valve driver board, 3x 1 byte
(6bits of user data plus
2filler bits)
10 Input module (1byte of user
data)
1 byte of user data
11 Input module (1byte of user
data)
1 byte of user data
12 Output module (1byte of
user data)
1 byte of user data
Bus coupler 1byte of parameter
data
8bytes of diagnostic
data
Total length of output
data: 11 bytes
Total length of input
data: 12 bytes
The total length of the output data in the example configuration is 11bytes. Of
this, 10 bytes are the module output data and 1 byte is the bus coupler parame-
ter byte.
AVENTICS™ EtherNet/IP | R412018139-BAL-001-AG | English 32

Table of Contents

Other manuals for Emerson AVENTICS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson AVENTICS and is the answer not in the manual?

Emerson AVENTICS Specifications

General IconGeneral
BrandEmerson
ModelAVENTICS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals