5 CONNECTING CONTROL SIGNALS
TheELQ-actuatorhasaterminalcompartmentwitha
plugconnectorforcontrolsignals.
Allcontrolsignalscanbeconnectedtotheterminals
insidethiscompartment.Incaseofmaintenanceor
replacementofthevalve/actuatorunit,theterminal
compartmentcanbeunpluggedfromtheELQ-actu-
atorandpluggedintoanotheractuator.Youdonot
needtoreconnectallthecontrolwiring.
Note
- Beforeconnectingthepowersupplyconnect
alloptionsproperly(seeoptioninstructions).
- Useandmountcableglandsasrequiredby
nationalorlocallegislation.
- WhenIP65,IP67orNEMA4Xingressprotec-
tionisrequired,theelectricalentriesmustbe
ttedwithequivalentorhigherratedglands
orblindplugs.
ATEX Installation instructions
Seechapter1.2and1.3foruseofFlame-
proofELQactuatorsinATEXclassied
hazardousareas.
Warning
Terminalcompartmentmustbeelectronically
isolatedbeforeanydisassemblyisbegun.
5.1 Connecting “Open” and “Close” con-
trol signals
A24VDCsignalat1and3openstheactuator.A
signalat2and3closestheactuator.
Nosignal(orasignalatboth),theactuatorstops.