Chapter 5 Parameter Table 21
EV3200 Door Control Inverter User Manual
Parameter Name Setting range Min. unit Default Mod.
F9.07
Frequency (Hz) at the latest
fault
0.00Hz ~ 128.00Hz 0.01Hz 0.00Hz *
F9.08
Status of input terminal at the
latest fault
0 ~ 127 (0: OFF
1: ON)
CD/OD/X5/X4/X3/X2/X1
1 0 *
F9.09
Status of output terminal at the
latest fault
0 ~ 7 (0: OFF
1: ON)
PC3/PC2/PC1
1 0 *
F9.10
High digits of pulse counted
for door position at fault time
0 ~ 9999 (×10000) 1 0 *
F9.11
Low digits of pulse counted for
door position at fault time
0 ~ 9999 1 0 *
F9.12 High digit of OD times 0 ~ 9999 (×10000) 1 0 *
F9.13 Low digit of OD times 0 ~ 9999 1 0 *
F9.14 High digit of CD times 0 ~ 9999 (×10000) 1 0 *
F9.15 Low digit of CD times 0 ~ 9999 1 0 *
F9.16 Total operation time 0 ~ 65535 hours (max.) 1 hour 0 *
F9.17 Total running time 0 ~ 65535 hours (max) 1 hour 0 *
F9.18 Parameter initialization
0: no operation
1: Clear the record
2: Load defaults
3 ~ 100: reserved
1
0
×
F9.19 Software version No. 1.00 ~ 99.99 0.01
Actual version
No.
-
F9.20 Product configuration No. 3200 ~ 3299 1
Actual
configuration
No.
-
F9.21 Heatsink temperature 0 ~ 100°C 1 0 *
F9.22 Relay output polarity selection
0: relays PA1/PC1 and PA2/PC2 serve as output NC relays
1: relays PA1/PC1 and PA2/PC2 serve as output NO relays
1 0 ×