Maintenance
Liebert
®
GXT4
44
6.1.1 Battery Replacement Procedures
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the six screws on the battery door, as shown in Figure 42.
3. Lay the battery door and screws aside for reassembly.
Figure 42 Removing the front plastic bezel cover and battery door
4. Gently pull the battery wires out and disconnect the battery plugs and battery receptacles, as
shown in Figure 43.
Figure 43 Disconnecting the battery plug and battery receptacle (front view)
5. Grasp the battery handle and pull one of the internal battery packs out of the UPS, as shown in
Figure 44.
Repeat this step if both battery packs will be replaced. Each model has two battery packs
Front Bezel
Battery Door
Screws, 6
8000VA / 10,000VA model shown;
5000VA & 6000VA model arrangement is
the same except smaller
Battery
Connector
Battery
Receptacle
Battery
Receptacle
Battery
Connector
8000 / 10,000VA model
shown; 5000 / 6000VA
model arrangement is
the same except smaller