Specifications
55 Liebert
®
GXT4
Table 21 Battery run time, minutes
Number of External
Battery Cabinets
Load Percent
of Capacity
208/120 VAC RT Models 208 VAC RT Model
5 kVA 6 kVA 8 kVA 10 kVA 6 kVA (L630)
Internal Battery
10% 129 106 144 112 100
20% 52 46 69 48 50
30% 36 27 43 30 38
40% 25 19 28 21 26
50% 18 14 22 16 19
60% 14 11 18 12 15
70% 11 9 14 10 12
80% 9 7 11 8 10
90% 8 5 10 6 9
100% 6 5 8 5 8
Internal Battery
+ 1 External
Battery Cabinet
10% 217 188 312 201 200
20% 131 108 145 120 132
30% 82 67 102 73 98
40% 53 46 71 49 73
50% 45 37 50 40 52
60% 37 28 43 31 46
70% 28 23 36 26 40
80% 25 19 28 21 34
90% 21 16 26 18 28
100% 18 14 22 16 25
Internal Battery
+ 2 External
Battery Cabinets
10% 341 321 428 330 345
20% 165 152 199 157 205
30% 133 109 146 121 150
40% 100 77 113 82 124
50% 74 53 92 64 101
60% 53 47 71 49 80
70% 48 40 53 43 68
80% 42 33 48 37 52
90% 37 27 43 31 49
100% 31 25 38 27 46
Internal Battery
+ 3 External
Battery Cabinets
10% 438 424 450 430 433
20% 221 192 314 204 316
30% 158 143 180 149 196
40% 134 109 147 122 157
50% 106 82 126 95 138
60% 83 68 103 73 113
70% 70 51 82 60 101
80% 53 46 71 49 83
90% 49 41 60 44 75
100% 45 36 50 40 67