Specifications
51 Liebert
®
 GXT4
™
Table 15 UPS specifications—Liebert GXT4-6000RTL630
Model Number GXT4-6000RTL630
Model Rating
4200W/6000VA
Dimensions, Rack Mount, W X D X H, in. (mm)
Unit 16.9 x 22.6 x 8.5 (430 x 574 x 217)
Shipping 20.3 x 29.3 x 20.9 (516 x 745 x 530)
Weight, lb (kg)
Unit 132.2 (60)
Shipping 156.5 (71)
Input AC Parameters
Nominal Operating Frequency  50 or 60Hz (Factory Default, 60)
Factory Default VAC  208VAC
User Configurable VAC
208/220/230/240VAC
(may be modified with configuration program)
Operating Voltage Range Without Battery Operation 176 – 280VAC
Maximum Allowable VAC 280VAC
Input Frequency Without Battery Operation 40 - 70Hz
Input Power Connection L6-30P Plug (on PD-L630 power distribution box)
Output AC Parameters
Factory Default VAC 208
Output Connections
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Duration Inverter Will Support Rated Load
105% to 130% 1 Minute
131% to 150% 10 seconds
151% to 200% 1 second
>200% (impact load) At least 5 cycles
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C) 32 to 104 (0 to 40); No Derating
Storage Temp, °F (°C) 5 to 122 (-15 to 50)
Humidity 0% to 95% Relative Humidity, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise
Less than 55dBA at 3.2ft. (1m) rear;
Less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety UL 1778, c-UL Listed
EMI/EMC FCC Class A
ESD EN61000-4-2
Radiated Susceptibility EN61000-4-3
Electrical Fast Transient EN61000-4-4
Surge Immunity EN61000-4-5
Transportation ISTA Procedure 1E