Chapter 5 iCOM Controller 53
Table 5-8 Descriptions of DISPLAY SETUP parameters
Parameters Default Setting range Description
U401 LANGUAG EN
RUS, CZE, CHI,
ESP, FRE, ITA,
DEU, EN, POR
Language options
U402 YEAR 2005 - Current year
U402 MONTH 04 01 ~ 12 Current month
U402 DAY 19 01 ~ 31 Current day
U403 HOUR 19h - Current hour
U403 MINUTE 8min - Current minute
U403 SECOND 17s - Current second
U404 TEMP F/C °C °F, °C Temperature indication
U405 CONTRAST 50% 0% ~ 100% Display contract
U406 BUZ FREQ 50% 0% ~ 100% Buzzer frequency. 0% means buzzer silenced
U406 BUZ TEST Off On, Off
Buzzer frequency test switch. It determines whether or not there
will be sound accompanying the adjustment of BUZ FREQ
through the setting
U407 BACKLITE 5min
5min, 10min,
30min, 1hr, 12hr
Backlight time, or the backlight time when there is no button
operation
U408 SCREEN Graph
Graph, Simple,
SimCo, GraCo
Main interface display mode
U409 SHOWS A + S SET, ACT, A + S
Main interface display mode of setpoints and actual values.
Range:
SET: only setpoints of the temperature and humidity are
displayed.
ACT: only actual temperature and humidity are displayed.
A + S: both setpoints and actual values of the temperature and
humidity are displayed
U410 DISPLAY Norm Norm (normal), Inv Display color
U411 DATE m/d/y m/d/y, d.m.y, y-m-d Date display format
5.6.8 TOTAL RUN HRS
The TOTAL RUN HRS menu records the total run time (unit: hr) of the system components. You can also set the run
time limits of the system components through this menu. If the actual component run time exceeds the set limit, alarms
will be raised.
This menu requires password. You can reset the total run time to zero in order to restart timing.
Note
Resetting the timers is not needed unless the components are replaced.
The parameters on this menu are described in Table 5-9. Each component has a LIMIT option to set the run time limit
of the corresponding component.
Table 5-9 Descriptions of TOTAL RUN HRS parameters
Parameters Default Related component Parameters Default Related component
U502 MOTOR(S) 1000hr U507 EL HEAT1 34hr
U502 LIMIT 32000hr
Fan motor
U507 LIMIT 32000hr
Electric heater 1
U503 COMP1 500hr U508 EL HEAT2 45hr
U503 LIMIT 32000hr
Compressor 1
U508 LIMIT 32000hr
Electric heater 2
U504 COMP2 500hr U509 EL HEAT3 0hr
U504 LIMIT 32000hr
Compressor 2
U509 LIMIT 32000hr
Electric heater 3
U505 CW/FC 1000hr U510 HUM 7hr
U505 LIMIT 32000hr
Chilled water/free
cooling
U510 LIMIT 32000hr
Humidifier
U506 HG/HW 23hr U511 DEHUM 1hr
U506 LIMIT 32000hr
Hot gas/hot water
U511 LIMIT 32000hr
Dehumidification
Liebert.PEX2 Series Air Conditioner User Manual