80 Chapter 6 Application Of INTELLISLOT
5. On the main interface, typing ‘5’ can view whether the communication status between the communication card and
the Liebert.PEX series air conditioner is normal, as shown in the following figure.
6.3.4 Setting SNMP Parameters Of TCP/IP Communication Card
After the HyperTerminal of the TCP/IP communication card is set, you can set the parameters of this communication
card. The detailed setting procedures are as follows:
1. Type the IP address of the TCP/IP communication card in the address bar of the IE browser. If the interface shown
in Figure 6-8 appears, it indicates that the communication between the communication card and the iCOM controller is
abnormal. If the
State shows Completing or In Process, it indicates that the communication card is communicating
with the iCOM controller.
Figure 6-8 Initial interface (1)
Liebert.PEX2 Series Air Conditioner User Manual