68 Chapter 5 iCOM Controller
Analog output related settings
Table 5-35 Descriptions of analog output related settings
Factory 7/9 Default Setting range Description
A157
ANOUT1LO 0% 0 ~ 100%
A157
ANOUT1HI 100% 0 ~ 100%
A158
ANOUT2LO 0% 0 ~ 100%
A158
ANOUT2HI 100% 0 ~ 100%
A159
ANOUT3LO 0% 0 ~ 100%
A159
ANOUT3HI 100% 0 ~ 100%
A160
ANOUT4LO 0% 0 ~ 100%
A160
ANOUT4HI 100% 0 ~ 100%
A161
FS HE/HU 100% 0 ~ 100%
-
A163
ANOUT1 No -
A164
ANOUT2 No -
A165
ANOUT3 No -
A166
ANOUT4 No -
Analog output selection. See Table 5-36
Table 5-36 Descriptions of analog output options
Options Description Options Description
CW010 CW/FC 0 ~ 10V ALBD2 AlarmBoard 2
HW Hot water ALBD3 AlarmBoard 3
HW175 Hot water 1.75 IVAR I-Variex 1
VSD Variable fan speed drive HUM% HT HUM
COOL Cooling SUP Supply Temperature
CV175 CW/FC 1.75 RET Return Temperature
COOL1 Cooling 1 HUMI Humidifier
COOL2 Cooling 2 SUPSA Supersaver
HEAT Heater INVCO Inverted Cool
No No use HEAT3 Heating 33%
MBV1 Motorized ball vavle1 CW210 CW/FC 2 ~ 10V
MBV2 Motorized ball vavle 2 C2010 CW2 0 ~ 10V
SCR Silicon controlled rectifier C2175 CW2 1.75
CONF Configurable C2210 CW2 2 ~ 10V
ALBD1 AlarmBoard 1
Analog action related settings
Table 5-37 Descriptions of analog action related settings
Parameters (8/9) Default Setting range Description
A168 AO1 STA 0% 0% ~ 100% Analog output 1 start percentage
A168 AO1 STA 0V 0V ~ 10V Analog output 1 start voltage
A169 AO1 END 100% 0% ~ 100% Analog output 1 end percentage
A169 AO1 END 10V 0V ~ 10V Analog output 1 end voltage
A170 AO2 STA 0% 0% ~ 100% Analog output 2 start percentage
A170 AO2 STA 0V 0V ~ 10V Analog output 2 start voltage
A171 AO2 END 100% 0% ~ 100% Analog output 2 end percentage
A171 AO2 END 10V 0V ~ 10V Analog output 2 end voltage
A172 AO3 STA 0% 0% ~ 100% Analog output 3 start percentage
A172 AO3 STA 0V 0V ~ 10V Analog output 3 start voltage
A173 AO3 END 100% 0% ~ 100% Analog output 3 end percentage
A173 AO3 END 10V 0V ~ 10V Analog output 3 end voltage
A174 AO4 STA 0% 0% ~ 100% Analog output 4 start percentage
A174 AO4 STA 0V 0V ~ 10V Analog output 4 start voltage
A175 AO4 END 100% 0% ~ 100% Analog output 4 end percentage
A175 AO4 END 10V 0V ~ 10V Analog output 4 end voltage