3.7 Wire the Channel B mA output
To wire the mA output in explosion-proof, intrinsically safe, or nonhazardous installations,
follow this procedure.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 3-8: Channel B mA output wiring (externally powered)
A. mA HART output
B. Supply Voltage (See Figure 3-2.)
C. Loop Resistance (See Figure 3-2 for maximum loop resistance.)
D. Input device
3.8 Wire Frequency/Discrete output (Channel B)
Use this procedure to wire the externally-powered Frequency Output or Discrete Output
for Channel B.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Wiring the channels Installation Manual
April 2019 MMI-20058013
30 Micro Motion
®
4200 2-Wire Transmitter