9.3.7     7yyy / 9999 - Erasing data from the 
SMARTCARD
Data can be erased from the SMARTCARD one data block at a time or 
with data blocks 1 to 499 in selected together.
• Setting 7yyy in Pr xx.00 will erase SMARTCARD data block yyy
• Setting 9999 in Pr xx.00 will erase SMARTCARD data blocks 1 to 
499
9.3.8     9666 / 9555 - Set / clear SMARTCARD warning 
suppression flag
1. If the Solutions Module(s) installed to the source and destination 
drive are different, or are in different slots, the drive will produce a 
'C.Optn' trip. 
2. If the data is being transferred to a drive of a different voltage or 
current rating a 'C.rtg' trip will occur. 
It is possible to suppress these trips by setting the warning suppression 
flag. If this flag is set the drive will not trip if the Solutions Module(s) or 
drive ratings are different between the source and the destination drives. 
The Solutions Module or rating dependent parameters will not be 
transferred.
• Setting 9666 in Pr xx.00 will set the warning suppression flag
• Setting 9555 in Pr xx.00 will clear the warning suppression flag
9.3.9     9888 / 9777 - Set / clear the SMARTCARD read 
only flag
The SMARTCARD may be protected from writing or erasing by setting 
the read only flag. If an attempt is made to write or erase a data block 
when the read only flag is set, a 'C.rdo' trip is initiated. 
When the read only flag is set only codes 6yyy or 9777 are effective.
• Setting 9888 in Pr xx.00 will set the read only flag
• Setting 9777 in Pr xx.00 will clear the read only flag
9.4      Data block header information
Each data block stored on a SMARTCARD has header information 
detailing the following:
• A number which identifies the data block (Pr 11.37)
• Type of data stored in the data block (Pr 11.38)
• Drive mode if the data is parameter data (Pr 11.38)
• Version number (Pr 11.39)
• Checksum (Pr 11.40)
• Read-only flag
• Warning suppression flag
The header information for each data block that has been used can be 
viewed in Pr 
11.38
 to Pr 
11.40
 by increasing or decreasing the data block 
number set in Pr 
11.37
.
If Pr 11.37 is set to 1000: the checksum parameter (Pr 11.40) shows the 
number of bytes left on the card in 16 byte pages.
If Pr 11.37 is set to 1001: the checksum parameter (Pr 11.40) shows the 
total capacity of the card in 16 byte pages. Therefore, for a 4kB card this 
parameter would show 254.
If Pr 11.37 is set to 1002: the checksum parameter (Pr 11.40) shows the 
state of the read-only (bit 0) and warning suppression flags (bit 1).
If there is no data on the card: Pr 11.37 can only have values of 0 or 
1000 to 1002.
9.5      SMARTCARD parameters
This parameter shows the number of the data block last parameter or 
difference from default data block transferred from a SMARTCARD to 
the drive.
This parameter shows the data blocks that are stored on a 
SMARTCARD with header information, including a number to identify 
the data block.
This parameter gives the type/mode of the data block selected with 
Pr 11.37 as shown in the following table.
Table 9-4 Pr 11.38 types and modes
This parameter gives the version number of the data block.
This parameter gives the checksum of the data block, space left on the 
card, the total space on the card or the card flags. Refer to Pr 11.37 for 
information.
11.36 SMARTCARD parameter data previously loaded
RO Uni NC PT US
Ú
0 to 999
Ö
0
11.37 SMARTCARD data number
RW Uni NC
Ú
0 to 1002
Ö
0
11.38 SMARTCARD data type/mode
RO Txt NC PT
Ú
0 to 18
Ö
Pr 11.38 String Type/Mode
0 FrEE Value when Pr 11.37 = 0
13C.SE
Commander SE mode parameter file 
(not used)
2 3OpEn.LP Open-loop mode parameter file
3 3CL.VECt Closed-loop vector mode parameter file
4 3SErVO Servo mode parameter file
5 3REGEn Regen mode parameter file
6 3DC DC mode parameter file
7 3Un Unused
8 3Un Unused
94C.SE
Commander SE mode difference from default 
file (not used)
10 4OpEn.LP Open-loop mode difference from default file
11 4CL.VECt
Closed-loop vector mode difference from 
default file
12 4SErVO Servo mode difference from default file
13 4REGEn Regen mode difference from default file
14 4DC DC Mode difference from default file
15 & 16 4Un Unused
17 LAddEr Onboard Application Lite user program file
18 Option
A file containing user defined data (the file is 
normally created by an SM-Applications 
Solutions Module)
11.39 SMARTCARD data version
RW Uni NC
Ú
0 to 9999
Ö
0
11.40 SMARTCARD data checksum
RO Uni NC PT
Ú
0 to 65335
Ö
0