7.3.2 Select the discovered drive
1. Select the ‘Online’ icon to connect with the drive. When a successful connection is made the icon will
be highlighted orange.
2. Select ‘Set mode and region’.
If the required control mode is highlighted in the ‘Drive Settings’ dialog, then:
• Change the supply frequency, if required and select ‘Apply’, otherwise select ‘Cancel’.
• Select ‘Default parameters‘ from the Dashboard and in the ‘Default Parameters’ dialogue,
select ‘Apply’
If the required control mode is not highlighted in the ‘Drive Settings’ dialog then:
• Select the required mode and supply frequency.
• Select ‘Apply’.
3. Select ‘Set-up’ and perform the steps highlighted (dotted lines indicate a step which may not need to be
performed (see below):
4. Select 'Save parameters in drive' to perform a parameter save. The drive is now ready to run.
Action Detail
Motor Set-up
Powerdrive Connect contains a database for induction motors and permanent magnet
motors. Provision is also made to enter motor nameplate data.
The next section describes the use of the motor database for a Leroy Somer LSRPM motor
used in RFC-S Sensorless mode.
Analog I/O
The motor thermistor can be selected in Pr 07.011. Refer to the parameter help for
Pr 07.011 for further information.
Ramps Set-up Enter the required Acceleration rate and Deceleration rate
Autotune
Not required when using data from the motor database for a Leroy Somer LSRPM motor
used in RFC-S Sensorless mode.