15
Safety Manual
00809-0200-5100, Rev GB
Installation and Configuration
February 2017
Installation and Configuration
4.1.3 Connecting the Rosemount 2410 to the 5900
The SIL alarm input connection is located in the Exi terminal block as illustrated below.
Figure 4-3. 2410 IS terminal block
Table 4-3. Terminal assignment for 2410 IS terminal block
Terminal Designation Function
1a FB + Intrinsically Safe (FISCO) Tankbus positive (+) terminal
1b FB + Intrinsically Safe (FISCO) Tankbus positive (+) terminal
2a FB - Intrinsically Safe (FISCO) Tankbus negative (-) terminal
2b FB - Intrinsically Safe (FISCO) Tankbus negative (-) terminal
3 IS I/O+ IS Input/Output +
4 IS I/O - IS Input/Output -
5 Alarm - SIL Alarm -
(connect to terminal block on Rosemount 5900)
6 Alarm + SIL Alarm +
(connect to terminal block on Rosemount 5900)
GND_1 GND_1 Housing chassis/Tankbus shield
GND_2 GND_2 Housing chassis/Tankbus shield
Ground screw
SIL Alarm
Ta nk bus
FB+
FB-
Ground screw
IS (Exi)
compartment