Safety Manual
00809-0200-5100, Rev GB
Installation and Configuration
February 2017
Installation and Configuration
4.2.9 Changing the current alarm configuration
In case you have to change the current configuration of a Rosemount Tank Gauging Safety
System, it has to be unlocked, i.e. Safety Mode must be set to Not Approved. Once the system is
unlocked, the system can be configured in the same way as when setting up the Rosemount
Tank Gauging Safety System.
Note
The Rosemount 5900 Radar Level Gauge is not safety-rated during maintenance work,
configuration changes, or other activity that affects the Safety Function. Alternative means
should be used to ensure process safety during such activities.
To change the current configuration of a Rosemount Tank Gauging Safety System:
1. Start the TankMaster WinSetup configuration program. Ensure that you are logged on
as Administrator.
2. In the WinSetup workspace, click the right mouse button on the Rosemount 5900
Radar Level Gauge icon.
3. Choose the Properties option. The RLG Properties window appears.
4. Select the Advanced Configuration tab.
5. Click the Safety Alarm button.
Response: the Safety Alarm window appears.