23
Safety Manual
00809-0200-5100, Rev GB
Installation and Configuration
February 2017
Installation and Configuration
Figure 4-10. Tank Geometry for a Rosemount 5900 with Array Antenna and Proof Test
Reference Reflector
See the Rosemount 5900 Manual Supplement (Document No. 00809-0200-5900) for
instructions on how to install and configure a Proof Test Reference Reflector.
Section “SIL High Alarm test” on page 55 provides a description of how to perform a SIL High
Alarm test by using the Proof Test Reference Reflector.
Table 4-7. SIL Reference Reflector Distance
Antenna
SIL Reference Reflector Distance
Array 6 inch 1100 - 8000 mm
Array 8 inch 1400 - 8000 mm
Minimum 500 mm
Proof Test
Reference Reflector
SIL Reference Point
SIL High Alarm Limit
SIL Surface Distance
Measuring Range
SIL Low Alarm Limit
SIL Used Hold Off
SIL Reference Reflector Distance