28
Safety Manual
00809-0200-5100, Rev GB
Installation and Configuration
February 2017
Installation and Configuration
Example
Table 4-10. Example of how to configure the SIL High Alarm Limit
The calculated SIL High Alarm Limit in this example is 2620 mm. This is well above 625 mm
which is the minimum value that can be used for a Parabolic antenna at a maximum level rate of
2 mm/s as given by Tabl e 4- 9.
In case the SIL Hold Off Distance is adjusted, the SIL Hold Off Distance Adjustment value (see
Tab le 4- 13 ) must be added to the minimum value given by Ta ble 4 -9 .
Antenna Parabolic
Desired SIL High Alarm Limit (as measured from the SIL Reference
Point)
2500 mm
Maximum Level Rate that may occur in the tank 1.5 mm/s
Margin to add (Level Rate<2 mm/s) 120 mm
SIL High Alarm Limit to be configured in TankMaster 2500+120=2620
mm