Table 9-5 Menu 5 Regen parameter descriptions
In Regen mode the supply frequency is shown. Negative values indicate negative phase rotation of the supply.
This is the modulus of the r.m.s. fundamental line to line voltage at the inverter output.
The output power is the dot product of the output voltage and current vectors. Positive power indicates power flowing from the supply to the drive, and
negative power indicates power flowing from the drive to the supply.
Voltage across the internal DC bus of the drive.
Parameter
Range(
Ú) Default(Ö)
Type
5.01 Output / supply frequency ±100.0 Hz RO Bi FI NC PT
5.02 Output / supply voltage 0 to AC_VOLTAGE_MAX V RO Uni FI NC PT
5.03 Output / supply power ±POWER_MAX kW RO Bi FI NC PT
5.05 DC bus voltage 0 to +DC_VOLTAGE_MAX V RO Uni FI NC PT
5.07 Regen drive rated current 0 to RATED_CURRENT_MAX A RW Uni US
5.18 Maximum switching frequency 0 to 5 (3, 4, 6, 8, 12, 16 kHz) 0 RW Uni US
5.35 Disable auto-switching frequency 0 to 1 0 RW Uni US
RW Read / Write RO Read only Uni Unipolar Bi Bi-polar Bit Bit parameter Txt Text string
FI Filtered DE Destination NC Not cloned RA Rating dependent PT Protected US User save PS Power down save
5.01 Supply frequency
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
11111
Range Regen ±100.0 Hz
Update rate 250µs
5.02 Supply voltage
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 1111
Range Regen 0 to AC_VOLTAGE_MAX V
Update rate Background
5.03 Supply power
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
112111
Range Regen ±POWER_MAX kW
Update rate Background
5.05 DC bus voltage
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 1111 1
Range Regen 0 to +DC_VOLTAGE_MAX V
Update rate Background