When this bit is set to one the motor 2 parameters in menu 21 become active instead of the equivalent parameters in other menus. Changes will only
be implemented when the drive is disabled. When the motor 2 parameters are active the decimal point that is second from the right on the 1st row of
the display is lit. If this parameter is one when an auto-tune is carried out (Pr 5.12 = 1), the results of the auto-tune are written to the equivalent
second motor parameters instead of the normal parameters. Each time this parameter is changed the accumulator for motor thermal protection is
reset to zero.
Displays the number of the last set of defaults loaded, i.e. 1233, 1244, etc.
This parameter is used to start and stop the drive Onboard PLC program.
The drive Onboard PLC program status parameter indicates to the user the actual state of the drive Onboard PLC program. (not fitted / running /
stopped / tripped.)
11.45 Motor 2 parameters select
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111
Default Regen 0
Update rate Background
11.46 Defaults previously loaded
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1111
Range Regen 0 to 2,000
Default Regen Number of defaults loaded, i.e. 1,233 etc.
Update rate Background
11.47 Drive Onboard PLC program enable
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111
Range Regen 0 to 2
Default Regen 2
Update rate Background
Value Description
0 Halt the drive Onboard PLC program.
1
Run the drive Onboard PLC program (if fitted). Any out-of-range parameter writes attempted will be clipped to the
maximum / minimum values valid for that parameter before being written.
2 Run the drive Onboard PLC program (if fitted). Any out-of-range parameter writes attempted will cause a drive trip.
11.48 Drive Onboard PLC program status
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111
Range Regen -128 to +127
Update rate Background
Value Description
-n
Onboard PLC program caused a drive trip due to an error condition while running rung n. Note that the rung
number is shown on the display as a negative number.
0 Onboard PLC program is not fitted.
1 Onboard PLC program is fitted but stopped.
2 Onboard PLC program is fitted and running.