Unidrive M702 Getting Started Guide 11
Issue Number: 4
Safety information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Basic parameters
(Menu 0)
Running the motor
NV Media Card
Operation
Further information
UL listing
information
Table 2-2 400 V drive ratings, cable sizes and fuse ratings
Table 2-3 575 V drive ratings, cable sizes and fuse ratings
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG AWG A kW hp A kW hp
03400025 5 6
gG
10
CC, J
or T*
1.5 1.5 18 18 3.4 1.1 1.5 2.5 0.75 1.0
03400031 6.6 10 10 1.5 1.5 16 16 4.5 1.5 2 3.1 1.1 1.5
03400045 9.1 10 10 1.5 1.5 14 14 6.2 2.2 3 4.5 1.5 2.0
03400062 13.1 20 20 2.5 2.5 14 14 7.7 3 5 6.2 2.2 3.0
03400078 13.4 20 20 2.5 2.5 14 14 10.4 4 5 7.8 3 5.0
03400100 15.8 20 20 2.5 2.5 12 12 12.3 5.5 7.5 10 4 5.0
04400150 18.7 25
gG
25
CC, J
or T*
6 6 10 10 18.5 7.5 10 15 5.5 10.0
04400172 24.3 32 30 8 8 8 8 24 11 15 17.2 7.5 10.0
05400270
29
40
gG
35
CC, J
or T*
668830
15 20
27 11
20
05400300 40 35 6 6 8 8 31 30 15
06400350 36 63
gR
40
HSJ or
DFJ
10 10 6 6 38 18.5 25 35 15 25
06400420 46 63 50 16 16 4 4 48 22 30 42 18.5 30
06400470 60 63 70 25 25 3 3 63 30 40 47 22 30
07400660 74 100
gG
80
CC, J
or T*
35 35 1 1 79 37 50 66 30 50
07400770 88 100 100 50 50 2 2 94 45 60 77 37 60
07401000 105 125 125 70 70 1/0 1/0 112 55 75 100 45 75
08401340 155 250
gR
225
HSJ
2 x 50 2 x 50 2 x 1 2 x 1 155 75 100 134 55 100
08401570 177 250 225 2 x 70 2 x 70 2 x 1/0 2 x 1/0 184 90 125 157 75 125
09402000 232
315 gR
300
HSJ
2 x 70
(B1)
2 x 95
(B2)
2 x 3/0 2 x 2/0 221 110 150 180 90 150
09402240 267 350
2 x 95
(B1)
2 x 120
(B2)
2 x 4/0 2 x 4/0 266 132 200 224 110 150
10402700 332 400
gR
400
HSJ
2 x 120
(C)
2 x 120
(B2)
2 x 300 2 x 250 320 160 250 270 132 200
10403200 397 450 450
2 x 150
(C)
2 x 150
(B2)
2 x 350 2 x 300 361 200 300 320 160 250
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
575 V
Motor
power
@
575 V
Max.
cont.
output
current
Nom
power
@
575 V
Motor
power
@
575 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG AWG A kW hp A kW hp
05500030 4.3 10
gG
10
CC, J
or T*
0.75 0.75 16 16 3.9 2.2 3 3 1.5 2
05500040 5.7 10 10 1 1 14 14 6.1 4 5 4 2.2 3
05500069 9.3 20 20 1.5 1.5 14 14 10 5.5 7.5 6.9 4 5
06500100 13.2 20
gG
20
CC, J
or T*
2.5 2.5 14 14 12 7.5 10 10 5.5 7.5
06500150 18.7 32 25 4 4 10 10 17 11 15 15 7.5 10
06500190 24.3 40 30 6 6 10 10 22 15 20 19 11 15
06500230 29.4 50 35 10 10 8 8 27 18.5 25 23 15 20
06500290 37.1 50 40 10 10 6 6 34 22 30 29 18.5 25
06500350 46.9 63 50 16 16 6 6 43 30 40 35 22 30
07500440 45 50
gG
50
CC, J
or T*
16 16 4 4 53 37 50 44 30 40
07500550 62 80 80 25 25 3 3 73 45 60 55 37 50
08500630 83 125
gR
100
HSJ
35 35 1 1 86 55 75 63 45 60
08500860 104 160 150 50 50 1 1 108 75 100 86 55 75
09501040 166 150
gR
150
HSJ
2 x 70
(B2)
2 x 35
(B2)
2 x 1
2 x 3 125 90 125 104 75 100
09501310 166 200 175
2 x 50
(B2)
2 x 1 150 110 150 131 90 125
10501520 197
250 gR 250 HSJ
2 x 70
(B2)
2 x 70
(B2)
2 x 2/0 2 x 2/0
200 130 200 152 110 150
10501900 218
2 x 95
(B2)
200 150 200 190 132 200
Unidrive M702 Getting Started Guide English iss3.book Page 11 Friday, August 29, 2014 2:33 PM