12 Unidrive M702 Getting Started Guide
Issue Number: 4
Table 2-4 690 V drive ratings, cable sizes and fuse ratings
*These fuses are fast acting.
Table 2-5 Protective ground cable ratings
Typical short term overload limits
The maximum percentage overload limit changes depending on the selected motor. Variations in
motor rated current, motor power factor and motor leakage inductance all result in changes in the
maximum possible overload. The exact value for a specific motor can be calculated using the
equations detailed in the Parameter Reference Guide. Typical values are shown in the table below:
Table 2-6 Typical overload limits
Generally the drive rated current is higher than the matching motor rated current allowing a higher
level of overload than the default setting. The time allowed in the overload region is proportionally
reduced at very low output frequency on some drive ratings.
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
690 V
Motor
power
@
690 V
Max.
cont.
output
current
Nom
power
@
690 V
Motor
power
@
690 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG AWG A kW hp A kW hp
07600190 20 25
gG
25
CC, J
or T*
10 10 8 8 23 18.5 25 19 15 20
07600240 26 32 30 10 10 6 6 30 22 30 24 18.5 25
07600290 31 40 35 10 10 6 6 36 30 40 29 22 30
07600380 39 50 50 16 16 4 4 46 37 50 38 30 40
07600440 44 50 50 16 16 4 4 52 45 60 44 37 50
07600540 62 80 80 25 25 3 3 73 55 75 54 45 60
08600630 83 125
gR
100
HSJ
50 50 2 2 86 75 100 63 55 75
08600860 104 160 150 70 70 1/0 1/0 108 90 125 86 75 100
09601040 149 150
gR
150
HSJ
2 x 50
(B2)
2 x 35
(B2)
2 x 1 2 x 3 125 110 150 104 90 125
09601310 171 200 200
2 x 70
(B2)
2 x 50
(B2)
2 x 1/0 2 x 1 155 132 175 131 110 150
10601500 202 225 gR
250 HSJ
2 x 70
(B2)
2 x 70
(B2)
2 x 2/0 2 x 1/0 172 160 200 150 132 175
10601780 225 250 aR
2 x 95
(B2)
2 x 3/0 2 x 2/0 197 185 250 178 160 200
Input phase conductor
size
Minimum ground conductor size
10 mm
2
Either 10 mm
2
or two conductors of the same cross-sectional area as the input phase
conductor (an additional ground connection is provided on sizes 3, 4 and 5 for this
purpose).
> 10 mm
2
and 16 mm
2
The same cross-sectional area as the input phase conductor
> 16 mm
2
and 35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the input phase conductor
Operating mode RFC from cold RFC from 100 %
Open loop
from cold
Open loop
from 100 %
Normal Duty overload with motor rated
current = drive rated current
110 % for 165 s 110 % for 9 s 110 % for 165 s 110 % for 9 s
Heavy Duty overload with motor rated
current = drive rated current (size 8 and
below)
200 % for 28 s 200 % for 3 s 150 % for 60 s 150 % for 7 s
Heavy Duty overload with motor rated
current = drive rated current (size 9E and
10)
170 % for 42 s 170 % for 5 s 150 % for 60 s 150 % for 7 s
Unidrive M702 Getting Started Guide English iss3.book Page 12 Friday, August 29, 2014 2:33 PM

Other manuals for Emerson Unidrive M702

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive M702 and is the answer not in the manual?

Emerson Unidrive M702 Specifications

General IconGeneral
BrandEmerson
ModelUnidrive M702
CategoryController
LanguageEnglish

Related product manuals