EasyManua.ls Logo

Emerson VERTIV Liebert Mini-Mate2 MM2CF - Figure 22 Unit Electrical Connections

Emerson VERTIV Liebert Mini-Mate2 MM2CF
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Site Preparation and Installation
33 Liebert
®
Mini-Mate2
Figure 22 Unit electrical connections
Interconnecting condenser
blower harness
Field-supplied 24V
(NEC Class 2 wiring)
to condensing module
(if applicable).
Field-supplied, field wired
thermostat wire to remote
wall box
Entrance for Customer
Low-Voltage Connections
Fan Speed Control captube
passage holes
Remote Humidifier Contact
Field-supplied 24V Class 2
wiring to Terminals 11 and 12,
located in field wire
compartment
Heat Rejection Connection.
Field-supplied 24V NEC Class 2 wiring.
See note 2. For remote air-cooled
units from Terminals TB2-1, 2, 3 and 4
in the Fan/Coil module to Wires 1, 2,
3 and 4 in the condensing module:
1. 24V GND
2. 24V Supply
3. High Pressure Alarm (OPT)
4. Hot Gas Bypass Connection
(Optional) Condensate Pump Auxiliary
Float Switch Connection to Terminal
TB1-8 and TB1-9.
Common Alarm Connection
Field-supplied 24V Class 2 wiring to
common alarm Terminal TB1-6 and
TB1-7
Remote Unit Shutdown. Replace existing
jumper between Terminals TB1-4 and TB1-5
with normally closed switch having a
minimum 75VA rating, use field-supplied
24V Class 1 Wire
Drycooler/Circulating pump
control circuit TB70-71. Optional
w/Econ-O-Cycle models. Use
field-supplied 24V Class 2 wire.
Customer Remote Alarm Connection
Field-supplied 24V Class 2 wiring to
Terminals TB1-1, TB1-2 and TB1-3.
Entrance for customer
low-volt connection
Site Monitoring Connection. Terminals
TB4-1 (+) & TB4-2 (-) are for connection
of a 2 wire, twisted pair, communication
cable (available from Emerson or others)
to optional Liebert SiteScan
NOTES:
1. Refer to specification sheet for full load amp and wire size amp ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.3mm) for up
to 75'(23m) or not to exceed 1 volt drop in control line.
Remote Control Wall Box Connection
to TB3-1,2,3, 4 connected with field-supplied
thermostat wire (22ga, shielded/jacketed.
Unit control board terminals marked GND,
+5V, T-, T+ must be connected to
corresponding terminals on remote
control wall box.
Earth Ground Connection
Connection terminal for field-
supplied earth grounding wire
Entrance for Customer
High-Volt Connection
High-Volt Power Connections.
Electric service connection
terminals.
Factory-installed disconnect
switch (optional)
DPN000175
Rev. 1
RIGHT
END

Table of Contents

Related product manuals