XWEB PRO 21/23
this option the system will become reachable outside the emergency procedure only on
IP:192.168.0.150; press on DATA RESET to avoid losing the network configuration (and the other
system configuration parameters); the system will then be reachable outside the emergency procedure
with the IP of "IP ADDRESS" present on the page described in the previous section.
7) Open the JMP contacts by disconnecting the jumper
8) Enter the credentials provided by Dixell Technical Support; the data of MAC ADDRESS and DATE must
be provided beforehand:
9) Press the "Confirm" key: if the data entered are correct the system will complete its operations and will
be restarted automatically. Warning: do not disconnect the power supply until XWEB completely restarts.
10) Wait a couple of minutes to complete the operation and the emergency procedure; it will now be possible
to log in with a username and password: Admin / Admin