Page 105
1.6.3 Phi monitoring
04. 07. 2015 10:44
phi min.error
phi circulation
t undercut
0.10l/min
1.00l/min
1.6.4 Emerg. OFF
04. 07. 2015 10:45
T limit Coll.1
Hyst.
100.0°C
5.0K
1.6.5 Sensor balan...
04. 07. 2015 10:46
TS1 Offset
TS2 Offset
TS3 Offset
TS4 Offset
0.0°C
0.0°C
0.0°C
0.0°C
PROFESSIONAL MODE
Long piping and other factors
may distort measured variables.
Here, an offset value can be
entered for each sensor.
Return to ›Main menu‹.
Continue with ›Login‹.
›T limit Coll. 1‹ or ›T limit Coll. 2‹ are used to
switch OFF the appropriate solar circuit
pumps to prevent destruction.
To protect the pump, the collector emergency
switch-off in solar circuits with high-efciency
pumps is reduced to 100°C.
Under ›Hyst‹, the value is entered by
which the limit temperature must be
undercut to cancel the forced shut-off.
Continue with ›Sensor balancing‹.
Here, the parameters for volume
ow monitoring are dened.
Continue with ›Coll. Emerg.OFF‹.