Software History
HART electronics
(operation using
Universal HART
Communicator DXR 275)
Note!
The entries in brackets indicate the matrix position in Commuwin II.
If you use the DXR 275 handheld terminal, you can access the parameter via Menu, see
Chapter 10.2 HART Matrix.
SW/
BA
Device
and
Software
No.
Device
Revision
DD
Revision
Changes
1.2 6512 1 2 –––––
3.0
from
09.94
6530 2 1 Operation Mode (V3H0) "Level manual" extended.
New parameters for the "Level manual" mode:
Manual Level, Table Editing (V3H6),
Row No. Table (V3H7),
Input Level (V3H8),
Set Volume (V3H9).
"Pressure before Bias", "Pressure after Bias" and
"Security Locking" parameters moved from the
Linearisation menu to the Service menu.
"Set Simulation Current" (V7H1)
Simulation limits extended from 3.8 to 22 mA.
"MIN Alarm" option for "Set Output Safety" (V0H8)
parameter no longer possible.
Error and warning list extended.
5.0
from
12.98
6550 5 1 "MIN Alarm" option for "Set Output Safety" (V0H8)
parameter available again.
"Set Simulation Current" (V7H1) parameter:
Simulations limits again 3.6 to 22 mA.
7.0
from
10.00
6570 7 1 Operation Mode (V3H0) "Pressure in %" extended.
New "Alarm Current Max" (V9H4) parameter.
Zero correction function:
New parameters for zero correction function,
refer to page 27
Zero Correction (V9H5),
Zero Correction Value (V9H6).
Editing limits:
Refer to Chapter 7.4
Download error E116, resettable using Reset 5140.
7.1
from
03.03
6571 7 2 Parameter names changed
old new (matrix position in brackets)
Set output safety Alarm mode (V0H8)
Min. (–10 %) Min. alarm
Max. (+110 %) Max. alarm
Continue Value hold
Min. pressure Peak hold P Min (V2H3)
Max. pressure Peak hold P Max (V2H4)
Min. temperature Peak hold T Min (V2H7)
Max. temperature Peak hold T Max (V2H8)
Low Sensor Cal Low Sensor Trim (V7H4)
High Sensor Cal High Sensor Trim (V7H5)
Set max. current Max. alarm current (V9H4)
Serial number HART Serial number (VAH2)
Calculation of the max. turn down changed.
Now: turn down = nominal value/set span,
previously: measuring range/set span
Note!