Error codes
on-site display
Code
Type Cause and Remedy Priority
E 670
2)
Warning 4 mA value was not transferred
The 20 mA value is outside the editing limits
1)
. As the span remains
constant during a change to the 4 mA value, the 20 mA value shifts
with the 4 mA value. This warning only appears when calibrating with
reference pressure using the Z– and Z+ keys.
Carry out the calibration again. The 20 mA value must be within
these editing limits. If necessary, set the 20 mA value to a smaller
value. After this, first calibrate the 4 mA value and then the 20 mA.
16
E 672
2)
Warning Editing limit
1)
for 4 mA value reached.
Lower or upper editing level reached for 4 mA value. This warning
appears when calibrating the 4 mA value without a reference
pressure using the Z+ or Z– keys. The value is not accepted.
Carry out the calibration again and make sure that the lower/upper
editing limits for the 4 mA value are not undershot or exceeded.
17
E 673
2)
Warning Editing limit
1)
for 20 mA value reached.
Lower or upper editing level reached for 20 mA value.
This warning appears when calibrating the 20 mA value without a
reference pressure using the S+ or S– keys. The value is not
accepted.
Carry out the calibration again and make sure that the lower/upper
editing limits for the 20 mA value are not undershot or exceeded.
18
E 674
2)
Warning Calibration error: turn down too big.
The maximum possible turn down was exceeded. This warning
appears during a calibration using the keys of the on-site operating
terminal. The value is not accepted.
Carry out calibration again. The pressure value for the calibration of
the 20 mA value may not be too close to 4 mA value.
19
E 675
2)
Warning Current pressure value outside the sensor limits.
The currently applied pressure for calibrating the 4 mA or 20 mA
values is outside the editing limits
1)
(calibration with reference
pressure and using the Z+ and Z– or S+ and S– keys). The value is
not accepted.
Carry out calibration again. The currently applied pressure for
calibrating the 4 mA and the 20 mA values must be within the editing
limits.
20
1) The editing limits are described in Chapter 7.4.
2) These error codes only appear on the on-site display.
Cerabar S 7 Diagnosis and Trouble-Shooting
Endress+Hauser 43