CM14 Commissioning
Endress+Hauser 19
Parameters Possible settings Description
Out 1
0/4 mA
Numerical value
0.000 to 99 999
0.0 mS/cm
Physical value which corresponds to the lower
range limit of the analog output.
When the configured value is undershot, the
current output is set to the saturation current
of 0/3.8 mA.
Out 1
20 mA
Numerical value
0.000 to 99 999
0.2 mS/cm(conductive)
200 mS/cm(inductive)
Physical value which corresponds to the upper
range limit of the analog output.
When the configured value is exceeded, the
current output is set to the saturation current
of /20.5 mA.
Out 2
0/4 mA
Numerical value –50 to 250 °C
0.0 °C
Temperature which corresponds to the
measuring range lower limit of the
temperature input.
When the configured value is undershot, the
current output is set to the saturation current
of 0/3.8 mA.
Out 2
20 mA
Numerical value –50 to 250 °C
100 °C
Temperature which corresponds to the
measuring range upper limit of the
temperature input.
When the configured value is exceeded, the
current output is set to the saturation current
of /20.5 mA.
Damping main value 0 to 60 s
0 s
Configuration of the damping for low-pass
filtering of the input signals.
Extended setup Advanced settings for the device, such as the
relay, limit values etc.
The functions are described in the following
section, →  19.
Manual hold Off, On Function for freezing the current and relay
outputs
6.5 Extended configuration (Extended setup menu)
You can access the main menu by pressing the 'E' key during operation. Navigate through the
available menus with the '+' and '–' keys. When the desired menu is displayed, press the 'E' key
to open the menu. Use the "x Back" option, which can be found at the bottom of each menu/
submenu, to move up one level in the menu structure.
Parameters Possible settings Description
System General settings
Tag Customized text, max. 16
characters
Default: Aa
Use this function to enter the device tag.
Temp. unit °C
°F
Setting for the temperature unit