Commissioning Deltabar S PROFIBUS PA
30 Endress+Hauser
5.4 Flow measurement
Before calibrating the Deltabar S, the impulse piping must be cleaned and filled with fluid.
5.4.1 Quick Setup menu for the Flow measurement – on-site display
!
Note!
See also Page 15, Section 4.2.3 "Function of the operating elements" and Page 16, 4.3 "On-site
operation via on-site display".
P01-xMD7xxxx-19-xx-xx-xx-076
Abb. 12: Quick Setup menu for Flow measuring mode
OPERATING MENU
MAXFLOW
MAX. PRESS. FLOW
POS. ZEROADJUST
DAMPINGVALUE
FlowPressure Level
MEASURED VALUE
QUICKSETUP
GROUPSELECTION
MEASURING MODELANGUAGE
On-site operation
Measured value display
On-site display: Switch from the measured value display to GROUP SELECTION with F.
GROUP SELECTION
Select MEASURING MODE.
MEASURING MODE
Select "Flow" option.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the measured value. You correct the MEASURED VALUE via
the POS. ZERO ADJUST parameter with the "Confirm" option, i. e. you assign the value 0.0 to the pressure present.
MAX. FLOW
Enter maximum flow of primary device. (See also layout sheet of primary device).
MAX. PRESS FLOW
Enter maximum pressure of primary device. (See also layout sheet of primary device).