EasyManua.ls Logo

Endress+Hauser Deltapilot M FMB50 - Page 129

Endress+Hauser Deltapilot M FMB50
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Appendix
Endress+Hauser 129
Expert È Diagnosis È Simulation
Parameter name Description
Simulation mode (112)
Selection
Switch on simulation and select the simulation mode.
Any simulation running is switched off if the measuring mode or level type (Lin. mode
(037)) is changed.
Options:
•None
Pressure, see also this table, "Sim. pressure" parameter
Level, see this table, "Sim. level" parameter
•Flow, see this table, "Sim. flow" parameter
Tank content, see this table, "Sim. tank cont." parameter
Current, see this table, "Sim. current" parameter
Alarm/warning, see this table, "Sim. error no." parameter
Cerabar M and Deltapilot M:
P01-FMX21xxxx-05-xx-xx-en-004
Deltabar M:
P01-PMD55xxx-05-xx-xx-en-007
Factory setting:
None
Sim. pressure (113)
Entry
Enter the simulation value.
See also "Simulation mode".
Prerequisite:
"Simulation mode" = Pressure
Switch on value:
Current pressure measured value
Sim. flow (114)
Entry
Enter the simulation value.
See also "Simulation mode (112)".
Prerequisite:
"Meas. mode" = Flow and "Simulation Mode" = Flow
Sim. level (115)
Entry
Enter the simulation value.
See also "Simulation mode".
Prerequisite:
"Measuring mode" = Level and "Simulation mode" = Level
P
PV
Simulation value pressure
Transducer Block
Simulation value level
Simulation value tank content
Sensor
Current
output
Pressure
Level
Damping
Position
adjust-
ment
Sensor
trim
Sim.
current
P
PV
Simulation value pressure
Transducer Block
Simulation value level
Simulation value tank content
Sensor
Current
output
Pressure
Level
Damping
Position
adjust-
ment
Sensor
trim
Sim.
current
Flow
Simulation value flow

Table of Contents

Other manuals for Endress+Hauser Deltapilot M FMB50

Related product manuals