Deltapilot M 4...20 mA HART Commissioning
Endress+Hauser 37
Measuring mode selection
Pressure unit selection
8.4 Position zero adjustment
The pressure resulting from the orientation of the device can be corrected here.
Parameter name Description
Measuring mode (005)
Selection
Menu path: Setup
Measuring mode
Select the measuring mode.
The operating menu is structured differently depending on the measuring mode
selected.
WARNING
!
Changing the measuring mode affects the span (URV)!
This situation can result in product overflow.
If the measuring mode is changed, the span setting (URV) must be verified and, if
necessary, reconfigured!
Options:
Pressure
Level
Factory setting:
Pressure
Parameter name Description
Press. eng. unit (125)
Selection
Menu path: Setup
Press. eng. unit
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
mbar, bar
mmH2O, mH2O, inH2O
•ftH2O
•Pa, kPa, MPa
•psi
mmHg, inHg
•kgf/cm
2
Factory setting:
mbar or bar depending on the sensor nominal measuring range, or as per order
specifications
Parameter name Description
Corrected press. (172)
Display
Menu path:
Setup Corrected press.
Displays the measured pressure after sensor trim and position adjustment.
If this value is not equal to "0", it can be corrected to "0" by the position adjustment.