Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
116 Endress+Hauser
9.4.2 Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in m
3
. The maximum volume is 5 m
3
and the maximum height is 4 m (13 ft). The density of the fluid is 1 kg/dm
3
. The device is mounted
below the level lower-range value.
Prerequisite:
The measured variable is in direct proportion to the pressure.
This is a theoretical calibration, i.e. the tank volume, tank height and density of the fluid are
known.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. For information
on how to perform position adjustment, ä 142, Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
For a description of the parameters mentioned, see
ä 134, Table 2: GROUP SELECTION MEASURING MODE
ä 155, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level standard"
ä 158, Table 11: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
MODE "Linear".
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
P01-PMP75xxx-19-xx-xx-xx-003
Fig. 28: Calibration without reference pressure –
dry calibration
1 See Table, Step 9.
2 See Table, Step 10.
3 See Table, Step 11.
4 See Table, Step 12.
4 m
–0.5 m
r = 1
kg
dm
3
V = 5 m
3