Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (via local operation and FieldCare)
Endress+Hauser 123
!
Note!
1. For this level mode, the measured variables %, volume and mass are available.
→ ä 166 ff.
2. You can also specify customer-specific units. See parameter descriptions for PRESS. ENG.
UNIT (060) (→ ä 155), HEIGHT UNIT (708) (→ ä 163), UNIT VOLUME (313) (→ ä 166)
and MASS UNIT (709) (→ ä 167).
3. Once you have selected the "Pressure linearized" level mode, the warning message "W710 Set
span too small. Not allowed." can appear. At this stage, the linearization table already consists
of two points as standard. It could be the case that the 2nd value, and thus the highest X-VAL.
of the linearization table, is smaller than the minimum span permitted (→ MINIMUM SPAN
(591), → ä 198). The message disappears as soon as the highest X-VALUE is greater than the
minimum span and the table entered is active.