5 Entries for the Measuring Point
5.1 Locking/Unlocking Parameters
Locking The parameters can be locked from the handheld terminal by entering a code
number between 1 and 11 or between 13 and 9998: all settings in the electronic insert
are protected from being altered. If the code number 9999 is shown in the display,
then locking has been activated at the electronic insert by pushbutton.
Step Entry Cursor in Display at Significance
1 2
EXTENDED CALIBRATION
Extended calibration
28
SECURITY LOCKING
Locking
12
No locking activated
3 e.g. 35
35
Selected code number for locking
4 F4
[ENTER]
Confirms entry, valueis transmitted
With the exception of "
SECURITY LOCKING"
all fields can be viewed but not changed..
Unlocking Locking can be again cancelled by entering the code number 12. This does not apply
if the locking was activated at the electronic insert. This is indicated by the code
number 9999 in the menu field.
Step Entry Cursor in Display at Significance
1 2
EXTENDED CALIBRATION
Extended calibration
28
SECURITY LOCKING
Locking
e.g. 35
35
Selected code number for locking
312
12
Code number for unlocking
4 F4
[ENTER]
Confirms entry, value to be transmitted
5.2 Tag Number
A measuring point number (
"SET TAG NUMBER"
) can be assigned to the electronic insert
by using the handheld terminal. This consists of 8 ASCII characters. This measuring
point tag serves to identify different electronic inserts connected to the same power
line as every electronic insert has to have its own unique tag number.
Step Entry Cursor in Display at Significance
1 4
USER INFORMATION
User information
21
SET TAG NUMBER
Locking
3 e.g. LIC10
LIC10
Enter up to 8 characters
4 F4
[ENTER]
Confirms entry, value is transmitted
5 Entries for the Measuring Point
Electronic insert FEC 12 (HART)
14 Endress+Hauser