EasyManua.ls Logo

Endress+Hauser Flowphant T DTT31 - Power Supply

Endress+Hauser Flowphant T DTT31
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DTT31, DTT35
Endress+Hauser 5
Inductive load To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid valves) when
directly connected to a protective circuit (free-wheeling diode or capacitor).
Power supply
Electrical connection Plug connection
!
Note!
DTT35: Electrical cables must comply with 3-A standard, must be smooth, corrosion resistant and cleanable.
T09-TTR31xxx-04-00-xx-xx-000
A: M12x1 connector
B: Valve connector M16x1.5 or NPT ½"
Device connection
DC voltage version with M12x1 connector
a0006818
Item No. Output setting Order code (see Ordering information section)
A1 1x PNP switch output DTT3x-A1A*******
A2 2x PNP switch output R1 and m (R2) DTT3x-A1B*******
A2’ 2x PNP switch output R1 and m (diagnosis/NC
contact with "DESINA" setting)
DTT3x-A1B*******
A3 1x PNP switch output and 1x analog output
(4 to 20 mA)
DTT3x-A1C*******