Commissioning TMT162
22 Endress+Hauser
!
Note!
The sensor inputs ( SW 01.03.00) are no longer available in the Commuwin II PC configuration
software.
Function group SENSOR 1
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Sensor type
IEC 751
JIS
IEC 751
Edison Copper
Winding No. 15
SAMA
Edison Curve
No. 7
GOST
Sensor type
Pt100
Pt200
Pt100
Pt500
Pt1000
Ni100
Ni1000
Cu10
Pt100
Ni120
Pt50
Pt100
Cu50
Cu100
Polynomial RTD
Callendar - van
Dusen (Pt100)
TC Type B
TC Type C
TC Type D
TC Type E
TC Type J
TC Type K
TC Type L
TC Type N
TC Type R
TC Type S
TC Type T
TC Type U
10 to 400 Ω
10 to 2000 Ω
-20 to 100 mV
Lower range
value
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-76 °F (-60 °C)
-76 °F (-60 °C)
-148 °F (-100 °C)
-148 °F (-100 °C)
-94 °F (-70 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
-328°F (-200 °C)
32 °F (0 °C)
32 °F (0 °C)
32 °F (0 °C)
-454 °F (-270 °C)
-346 °F (-210 °C)
-454 °F (-270 °C)
-328°F (-200 °C)
-454 °F (-270 °C)
-58 °F (-50 °C)
-58 °F (-50 °C)
-454 °F (-270 °C)
-328°F (-200 °C)
10 Ω
10 Ω
-20 mV
Upper range
value
1562 °F (850 °C)
1562 °F (850 °C)
1200 °F (649 °C)
482 °F (250 °C)
482 °F (250 °C)
482 °F (250 °C)
302 °F (150 °C)
500 °F (260 °C)
1292 °F (700 °C)
518 °F (270 °C)
2012 °F (1100 °C)
1562 °F (850 °C)
392 °F (200 °C)
392 °F (200 °C)
1562 °F (850 °C)
1562 °F (850 °C)
3308 °F (1820 °C)
4208 °F (2320 °C)
4523 °F (2495 °C)
1832 °F (1000 °C)
2192 °F (1200 °C)
2501 °F (1372 °C)
1652 °F (900 °C)
2372 °F (1300 °C)
3214 °F (1768 °C)
3214 °F (1768 °C)
752 °F (400 °C)
1112 °F (600 °C)
400 Ω
2000 Ω
100 mV
min. range
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
900 °F (500 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
10 Ω
100 Ω
5 mV
+
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
+
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
SW 01.03.00
V3H0
-
-
-
-
-
-
Specific linearization and sensor matching
Selecting the sensor types 'Callendar-van-Dusen' or 'Polynomial RTD' improves the accuracy of the system or defines user-specific linearization of resistance
thermometers. A detailed description of the 'Callendar-van-Dusen' method and 'Polynomial RTD' linearization is provided in the Appendix to these Operating
Instructions.
!
Note!
The selection list of the sensor type is displayed depending on the PV unit. Example:
When selecting a resistance thermometer the PV unit must first be set to Ω.
!
Note!
Sensor 1 has priority, sensor 2 setup is matched to the setup of sensor 1.
Example: Sensor 1 is set up for a 4-wire connection, sensor 2 is set up for a 3-wire
connection; there is an automatic change of sensor 2 to a type K thermocouple.