TMT162 Commissioning
Endress+Hauser 23
Sensor
connection
Input of RTD connection mode.
Input:
•2-wire
• 3-wire
•4-wire
!
Note!
Function is only active on selection of a resistance thermometers (RTD) in the
device function SENSOR TYPE (V3H0).
++V3H1
Cold junction Selection of the internal (Pt100) or an external comparison
measurement point.
Input:
• internal
•external
!
Note!
Function is only active on selection of a thermocouple (TC) in the device function
SENSOR TYPE (V3H0).
++V3H2
External
temperature
Input of the external comparison point measurement value.
Input: -40.0 to 185.0 °F / -40.00 to 85.00 °C (°C, F, K)
32 °F (0 °C)
!
Note!
Function is only active when "external" has been selected in the device function
COLD JUNCTION (V3H2).
++V3H3
2-wire
compensation
Input of cable resistance compensation on a 2-wire RTD connection.
Input: 0.00 to 30.00 Ω
!
Note!
Function is only active when a 2-wire connection has been selected in the device
function SENSOR CONNECTION (V3H1).
++V3H4
Offset Input of the zero point correction (offset).
Input: -18.00 to 18.00 °F (-10.00 to 10.00 °C)
32.0 °F (0.00 °C)
++V3H5
Measurement
unit
Display of measurement unit.
Sensor 1 unit = PV unit
++V3H6
Serial no.
sensor
Input of the serial number of the sensor connected to this sensor input. + + V3H7
Function group SENSOR 1
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Function group SENSOR 2 (only on a device with 2 sensor inputs)
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Sensor type See Function group SENSOR 1
!
Note!
Sensor 1 has priority, sensor 2 setup is matched to the setup of sensor 1.
Example: Sensor 1 is set up for a 4-wire connection, sensor 2 is set up for a 3-wire
connection; there is an automatic change of sensor 2 to a type K thermocouple.
++V4H0