Commissioning TMT162
26 Endress+Hauser
Ambient alert An alarm for overshooting/undershooting of permitted ambient temperature is
deactivated here.
Input:
on
•off
!
Note!
If the ambient temperature alarm is deactivated then the unit will not go into alarm
but will transmit a warning. Change is the responsibility of the user.
++V2H2
Corrosion
detection
Sensor connection cable corrosion can lead to false measured value readings.
Therefore our unit offers the possibility to recognize any corrosion before the
measured values are affected. (see chapter 9.2.1).
There are 2 different steps selectable dependent on the application requirements:
off (warning output just before reaching the alarm set point. This allows for
preventative maintenance/trouble-shooting to be done.)
on (no warning, immediate alarm)
++V2H4
Alarm for
undershooting
/overshooting
Input:
Off
If the measuring range is undershot or overshot, the output signal is
temperature-linear up to 3.8 mA or 20.5 mA and remains at these values (as per
NAMUR NE43).
•On
An error is signalled if the measured temperature corresponds to an output value
< 3.8 mA or > 20.5 mA, (see 'Fault condition').
SW 01.03.00 SW 01.03.00 -
Mains filter Selection of mains filter
50 Hz
60 Hz (For North American region 60 Hz is default)
++V2H3
Function group SAFETY SETTINGS
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Function group DISPLAY
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Display Activating the values to be shown on the device display:
•Display: PV
Display: Sensor 1 value
Display: Sensor 2 value
Display: RJ value
Display Analog output value
•Display: Status
•Display: Time
Display: percentage value (on/off)
Primary value (PV) is displayed as a
percentage.
(DXR,CW=1)
(DXR,CW=2)
(DXR,CW=4)
(DXR,CW=8)
(DXR,CW=16)
(DXR,CW=32)
2s (DXR,CW=0)
4s (DXR,CW=64)
6s (DXR,CW=128)
8s (DXR,CW=192)
off (DXR,CW=0)
on (DXR,CW=64)
+
+
+
+
+
+
< SW 01.03.00
SW 01.03.00
+
+
+
+
+
+
< SW 01.03.00
SW 01.03.00
V6H0
V6H0
V6H0
V6H0
V6H0
V6H0
< SW
01.03.00
-