TMT162 Technical data
Endress+Hauser 47
Measured error Pt100: 0.18 °F (0.1 °C)
Output measured error: 0.04 °F (0.02 °C) (0.02% of 212 °F)
Input temperature drift: 0.054 °F (0.03 °C)
Output temperature drift: 0.018 °F * 1.5 = 0.03 °F (0.015 °C)
Max. possible error (total of errors): 0.3 °F (0.165 °C)
Δϑ = deviation of ambient temperature from the reference operating condition.
Total measuring point error = max. possible measured error + temperature sensor error.
Influence of the cold
junction
Pt100 IEC 60751 Cl. B (internal cold junction for thermocouples TC)
10.0.5 Environment conditions
Ambient temperature
limits
• Without display: -40 to 185 °F (-40 to +85 °C)
• With display: -40 to 158 °F (-40 to +70 °C)
For use in hazardous area, see Ex certification or control drawing
!
Note!
At temperatures < -4 °F (-20 °C) the display may react slowly.
Storage temperature • Without display: -40 to 212 °F (-40 to +100 °C)
• With display: -40 to 185 °F (-40 to +85 °C)
Altitude Up to 6560 ft (2000 m) above sea level according to IEC 61010-1 (EN 61010-1), CSA 1010.1-92
Climate class As per IEC 60 654-1, Class C
Degree of protection • IP67, NEMA 4x
• IP69K, (T17 housing)
Shock and vibration
resistance
3g / 2 to 150 Hz as per IEC 60 068-2-6
Electromagnetic
compatibility (EMC)
CE Electromagnetic Compatibility Compliance
The device meets all requirements listed under IEC 61326 Amendment 1, 1998 and
NAMUR NE 21
This recommendation is a uniform and practical way of determining whether the devices used in
laboratories and process control are immune to interference with an objective to increase its
functional safety.
Condensation Permitted
ESD (Electrostatic discharge) IEC 61000-4-2 6 kV cont., 8 kV air
Electromagnetic fields IEC 61000-4-3 0.08 to 2 GHz
80 to 750 MHz
1.4 to 2 GHz
10 V/m
30 V/m
30 V/m
Burst (fast transient) IEC 61000-4-4 2 kV
surge IEC 61000-4-5 0.5 kV sym.
Conducted RF IEC 61000-4-6 0.01 to 80 MHz 10 V