Levelflex FMP56, FMP57
Endress+Hauser 27
Mounting in non-metallic vessels
1
2
A0012527
1 Non-metallic vessel
2 Metal sheet or metal flange
To measure, Levelflex with a rod probe needs a metallic surface at the process connection. Therefore:
Select an instrument version with metal flange (minimum size DN50/2").
Or: mount a metal sheet with a diameter of at least 200 mm (8") to the probe at the process connection. Its
orientation must be perpendicular to the probe.
Installation with heat insulation
If process temperatures are high, the device must be included in normal tank insulation to prevent the
electronics heating up as a result of heat radiation or convection.
The insulation may not exceed beyond the points labeled "MAX" in the drawings.
Process connection with thread
MAX
max.150°C(302°F)
1
A0014143
1
Tank insulation